33KV Dropout Fuse Cutout
33-36kv Polymer Dropout Fuse Cutout
Product Picture

Description
Drop-out fused cut out and load Switching fuse cutout are of outdoor used high voltage protective device. To be connected with incoming feeder of distribution line it mainly protect transformer or lines from short circuit and overload, and on/off loading current.
Components
Drop-out fused cut out is composed of insulator supports and fuse tube. Static contacts is fixed on insulator support and moving contact is installed on two ends of fuse tube.
Fuse tube is composed of:
1. Inside arc extinguishing tube
2. Outer phenolic compound paper tube or epoxy glass tube
Load switching fuse cutout provides enforced elastic auxiliary contacts and arc-extinguishing enclosure for switching on/off loading current.
Operating Principle
1. When working normally, fuse link tightened the fuse tube to be close position.
2. If system occur faults, big fault current melts fuse immediately and take place electric arc, which makes arc extinguishing tube being heated and explode a lot of gases. This will produce high pressure and blow off the arc along with tube.
3. After fuse-link melt moving contact has no tightened strength, mechanism is locked and fuse tube dropout.
4. Cutout now is in open position. Operator shall use insulating Link Rod to pull the moving contact.
Main Parameter
Type | Rated Voltage (kV) | Rated Current (A) | Breaking Current (A) | Impulse Voltage Bil (BIL) | Power Frequency withstand voltage | Leakage Distance (mm) | Weight (kg) | Dimension (cm) |
CRW-33 | 33 | 100 | 10000 | 170 | 70 | 850 | 12 | 90X40X17 |
CRW-33 | 33 | 200 | 12500 | 170 | 70 | 850 | 12 |
The Workshop

Hot Tags: 33kv dropout fuse cutout, China, 33kv dropout fuse cutout manufacturers, suppliers, factory, composite hollow core insulators, t track clamps, fuel hose clamps, Fuse Link for Dropout Fuse Cutout, 22 kv lightning arrester, worm drive hose clamps
You Might Also Like
Send Inquiry